EXCEL WEB CONTROL SYSTEM NETWORKING WHITE PAPER
- 5 - EN2B0396GE51 R1214
Network access via USB
The USB interface on the Excel Web allows establishing
network connections with client PCs/Laptops for the following
functionality and purpose:
Access via Internet Browser
Access via Honeywell CARE engineering tool
The following USB Ethernet host-to-host adapters will allow
this feature:
SMC 2208USB/ETH
SMC 2209USB/ETH
Belkin Direct Connect F5U104
D-Link Dub-100E (old silver model before 2012)
Wireless LAN
When installed in networks supporting wireless LAN, Excel
Web can be operated via Wireless LAN.
Depending on the mobile unit, the Excel Web can be
operated via Internet Browser and/or engineered with the
Honeywell CARE engineering tool.
Encryption
BACnet
BACnet communication is not encrypted yet. The current
BACnet drivers do not support encryption yet.
The password for ReinitializeDevice or backup and restore is
“<UserName>:<Password>”. This string is openly transmitted
via BACnet. The allowed users can be configured in the
CARE application. All users with the access level “Building
engineer” or higher can execute this function.
BACnet/IP can be used with VPNs.
Internet Browser Login
Internet Browser login uses an authentification mechanism
based on Session IDs and MD5 encryption. Neither User
Name nor Password are openly transmitted over the network.
There is an adjustable log off timeout, which can be set in the
Internet browser operation for Excel Web.
Terminal Login
Terminal login uses no encryption for the password.
FTP Login
FTP login uses no encryption for the password.
The password is frequently openly transmitted over the
network, when the Honeywell CARE engineering tool
connects to a controller.
RPC communication
The RPC communication is not encrypted. The Honeywell
CARE engineering tool uses the RPC communication to
configure the Excel Web controller.
Password Handling
Internet Browser Login
For the login with Internet Browsers every user needs a user
name and password.
The highest user level (SystemAdmin) needs a password
which must consist of 5 characters minimum, which is
defined in the Honeywell CARE engineering tool (CARE
project login password).
When operating the Excel Web via Internet, it is highly
recommended to use a “safe” password. By default the
CARE engineering tool will propose a “safe” password upon
creation of an Excel Web project in CARE.
FTP Login (Firmware 2.02.12 and older)
One FTP log-in exists:
Administrator the Administrator password can and
should be changed using the Honeywell CARE tool.
SSH Login (firmware 2.02.17 and
newer)
For the SSH log-in, two password levels exist:
SSH User a limited user which can only access one
single directory
Administrator the Administrator password can be
changed in the CARE project.
SNMP
Excel Web does not support the Simple Network
management Protocol.
Network Integration checklist
1) Involve Customer IT department right from the start of
the project concept phase!!
2) Agree on System Integrator responsibility.
Amongst others, this responsibility includes the
coordination of tasks listed under points 3) through
9) below.
3) Get contact details of one responsible person per
BACnet vendor that will integrate into the network.
4) Agree on level of BACnet Integration with customer
Work bottom up!
Start with defining the minimum functionality
required by the customer.
Once this is achieved, try to enhance the
interoperability.